Week2, 14th April
The PM that needs to do today will be carbon brush PM inspection. The instruction is check carbon brush and air filters. The carbon brush needs to be replaced when the measurement is less than 60mm. A normal carbon brush is 100mm long.
Besides the PMs, the condenser fan motor for air condition 1B at center control room also not function. Hence, we need to go to do the checking. Further checking had been done and found out that the condenser 1 motor winding is short circuit and wire for condenser 2 that connect to neutral is disconnected. After the adjustment and install the new motor, both the condenser is functioning.
Week2, 13th April

Week2, 12th April
Next is the steam turbine motors PM inspection. There are 2 inspections, general electrical and general physical inspection. For the electrical inspection, we checked for the on load current while for the physical inspection, we checked the bearing vibration and body temperature for the motor. There are 4 types of vibration need to be checked, that are non-driving end (NDE) X and Y axis and driving end (DE) X and Y axis. Each of them must be measured and the reading is recorded.
Week 1, 9th April
For diesel engine battery, we also do the same procedure. Besides that, we are required to take the reading for SG and voltage of the battery. The total voltage for a battery bank is around 24-27V.
In the evening, Mr. Sharif, supervisor of ECNI department, asked us to the control room to show how to switch on the water pump. Circuit breaker SF6 is used for 6.6kV and 415V circuit. When an accident occurred, circuit breaker is used to break the circuit.
The function of a differentiator of current is to check then three phases current is balanced or not. If it is not balance, it will sense by the current differentiator and circuit tripping will occurred.
The pump 1A is tested at the evening. Free running testing is used and after no error occurred, the connection with the shaft is connected and another testing is done. The vibration for the water pump after the repair had reduced.
Jockey pump
Diesel pump
Friday, April 16, 2010
Week 1, 8th April
In the pump hall, they also pump out the mug from the underground since it had been left unused for a long time. The installation process continue to the next day as it is a complicated system.